Scroll Top

What is a Solenoid Valve?

What is a solenoid valve and what is its primary function in fluid control systems?

A solenoid valve is an electrically controlled valve used to allow or prevent the flow of media through it. A solenoid valve works by having a plunger move up and down based on the magnetic field generated from the electrical solenoid. The plunger either opens or closes the orifice that the media flows through. There are different designs, construction material, and circuit functions allowing solenoid valves to be used in a wide array of applications. Since they electrically controlled, they can be controlled remotely and automatically

Solenoid control valves are electro-mechanical valves used to control the flow of liquids or gasses by shutting off the flow or allowing the flow using a solenoid to actuate the valve. They are used wherever the flow of fluid has to be automatically controlled.

What are the main components of a solenoid valve and their functions?

The valve body consists of the pressure containing parts in-contact with the process fluid. The solenoid converts electrical energy into a mechanical pull/push action. This consists of a coil of wire tightly wrapped around an iron core, and a ferromagnetic plug or plunger. Components vary depending on the design.

Nut: Holds the coil onto the valve and threads over the stop piece of the guide tube assembly.

Housing: Metal plate that covers the coil and helps complete the magnetic circuit created by the coil when energized.

Coil: Element of the valve that when energized creates a magnetic field.  Comprised of copper magnet wire spooled around a bobbin.

Flux Plate: Metal plate that helps complete the magnetic circuit with the housing.

Guide Assembly: Metal tube that internally houses the plunger, and acts as the external mounting post for the coil.  The magnetic stop piece is welded to the top and the flange is welded to the bottom.

Plunger Assembly: Magnetic plunger that is typically 430FR SS, including the plunger seal and spring.

O-Ring: Seal material that prevents the fluid from leaking external to the valve.  This seals the guide tube flange to the valve body.

Body: The portion of the valve that has the plumbing connections and also the seat for the plunger to seal on.

What materials are commonly used in the construction of solenoid valves to ensure durability and performance?

Solenoid valves are often available with various housing materials. Typical materials are Nylon (Polyamide – PA), PVC (PolyVinylChloride), Brass, Nickel plated brass and Stainless Steel (304 and 316). The material choice depends strongly on the chemical properties and the temperature of the medium

 What are the primary applications of solenoid valves in various industries?

Water Treatment
Solenoid valves are used in water treatment facilities to control the flow of chemicals, water, and wastewater. They help regulate the dosing of chemicals for disinfection and pH adjustment.

Irrigation systems
These devices play a crucial role in agricultural irrigation systems, allowing for automated control of water flow to different zones or fields.

Oil and gas
Solenoid valve in oil and gas industry, solenoid valves are employed for various purposes, such as controlling the flow of crude oil, natural gas, or hydraulic fluids in pipelines and equipment.

Manufacturing equipment
Such valves are used in machinery for manufacturing processes to control the flow of air, water, hydraulic fluids, and other liquids or gases.

Food and beverage
They are integral in the food and beverage industry for controlling the flow of ingredients, cleaning solutions, and gases during food processing and packaging.

Pharmaceuticals
These equipment are used in pharmaceutical manufacturing for precise control over the flow of pharmaceutical ingredients and fluids in production lines.

HVAC
Such devices are used in HVAC systems to regulate the flow of refrigerants, which is essential for maintaining proper temperature and humidity levels in buildings and equipment.

Automotive industry
Solenoid valve in automation is used in various applications, such as controlling the flow of fuel, air, and hydraulic fluids in engines and transmissions. They are also used in automotive air conditioning systems to control refrigerant flow.

Pneumatic control systems
These valves are a fundamental component in pneumatic control systems used in manufacturing and automation. They control the flow of compressed air to actuate pneumatic cylinders, grippers, and other automation devices.

Chemical industry
Such equipment is used in chemical processing plants to control the flow of corrosive or hazardous chemicals safely and accurately.

Waste Management
In waste management facilities, solenoid valves are used to control the flow of liquids and gases in processes like sewage treatment and landfill gas collection.

Aerospace Industry
Solenoid valves are used in aircraft and spacecraft for various purposes, including controlling the flow of fuel and hydraulic fluids

How do you determine the appropriate size and type of solenoid valve for a specific application?

There are five main parameters to consider when selecting a valve: Cv, media compatibility, pressure, temperature, and process fitting. For each of these parameters, maximum values are listed for each valve.

When considering what type of solenoid valve to employ, it is vital to understand the application into which the switch is to be introduced.

Important factors are:

  • Non energised state: Normally open or normally closed.
  • Flow Rate: The size of the valve (port size) dictates the maximum flow rate that can be achieved.
  • Electrical supply requirement: The voltage and current required to actuate the solenoid.
  • Electrical connection requirement.
  • The fluid type (to ensure chemical compatibility with the valve wetted parts).
  • Minimum and maximum working pressure.
  • Protection class requirement (IP rating).
  • Ambient and fluid temperature requirement.
  • Duty cycle required

What are the differences between normally open and normally closed solenoid valves?

They are typically normally open or normally closed. In short, a normally open valve allows flow through with no power and a normally closed valve stops flow with no power

Normally closed valves are designed to block flow through the valve and are commonly used for emergency safety. During usual operation, these devices use a spring to remain closed. The valve will open when the system begins to experience overpressure to ensure safety. Once pressure begins to normalize, it will automatically close.

Solenoid valves can also be normally closed. A solenoid valve is an electromechanical device that controls the flow of liquid or gas through a system. Normally closed solenoid valves include a plunger that remains in a closed position when the system is running smoothly, like pressure relief valves.

Normally closed solenoid valves also include a coil that, when powered, will cause the plunger to open and allow liquid or gas to pass through the valve.

Normally open valves are also used as safety devices. However, unlike normally closed valves, these parts work to maintain low pressure in a system. Normally open valves are designed to allow liquid or gas to flow through in usual circumstances. As the system builds pressure, they will begin to shut in order reduce and regulate pressure levels. In some extreme overpressure situations, they will close almost entirely.

There are normally open solenoid valves as well. These devices will remain open until power is sent to the coil and signals the plunger to close.

 

How does the design of a solenoid valve affect its response time and flow capacity?

From an electrical standpoint, the response of a solenoid valve is not instantaneous, since a certain amount of time must pass for the coil current to overcome the coil inductance. As a result, the magnetic flux takes a certain amount of time to reach its maximum after voltage is applied to the solenoid.

What are the common maintenance procedures for solenoid valves to ensure they function correctly?

Maintenance of your solenoid valve is vital to ensure that it continues to operate at an optimal level. Regular inspections of the valve’s components should be carried out to check for wear.

To inspect the valve’s components isolate the valve from voltage and fluid. Remove the top nut, I.D plate, coil and armature tube. Check for sediment, debris or corrosion inside the tube and valve body. Check that the armature/spring assembly moves freely inside the tube. Inspect the seals and o-rings for contamination or wear.

It should be possible to clean away small amounts of debris as long as care is taken not to damage the components further.

Damaged or worn components should be replaced.

 

How can solenoid valves be tested to ensure they are working properly and within specifications?

Connect the solenoid terminals to the required power source. For this, connect the positive terminal of the power source to one of the solenoid terminals and the negative terminal of the power source to the second terminal of the solenoid. This should bring continuity across its terminals.

Once the solenoid is connected to the power source, the circuit closes, and the solenoid should activate. There should be a click from the solenoid once the current is properly supplied. If there isn’t a click, the solenoid coil is bad, and the solenoid needs to be changed. To diagnose the solenoid, use a multimeter to test the solenoid for its resistance and voltage

Resistance testing

A resistance test ensures that the circuit within the solenoid is good condition.

Set the multimeter’s dial to measure resistance, represented by the Ω symbol on the meter.

Place the probes: The solenoid typically has three terminals; one is usually a peculiar-looking ground connection, while the other two look alike and are to be tested (or check the manufacturer’s manual to determine the terminals correctly). To test the solenoid, connect the multimeter probes to these terminals, ensuring that the connections are properly in contact with the terminals.

Note the multimeter readings:

The resistance reading can vary depending on the specific solenoid valve. Consult the manufacturer’s documentation to determine the expected resistance value range.

An ‘OL’ reading (infinite resistance) on the multimeter signifies an incomplete circuit within the solenoid (maybe from a bad coil or wire), and the solenoid needs to be replaced.

Voltage testing

A voltage test ensures that the solenoid receives or works with the right amount of voltage supplied by a power source.

Check the solenoid manual for specifications on whether the device works on AC or DC voltage. Rotate the multimeter dial and set it to measure AC (V~) or DC (V…) voltage.

Connect the multimeter probes to the solenoid terminals. Note the results. If the solenoid is operating normally, the multimeter reads a voltage that matches the rated voltage of the valve; otherwise, the coil is faulty and needs to be replaced.

Turn off the power supply to the solenoid valve and disconnect the multimeter probes.

 

What are the common failure modes of solenoid valves and how can they be mitigated?

It is important to identify whether the valve is stuck in the open or closed position in order to diagnose and solve the problem. Here are four potential solenoid valve failure modes and how to avoid them:

  1. Typical spool-style valves have large dynamic seals that dry out if not properly lubricated and maintained. The problem is, changing operating conditions (temperature, humidity, cycle rate) make it hard to predict when that maintenance will be required. Fluid contaminants can increase under extreme conditions, making the problem even worse. Direct-acting poppet valves are inherently less vulnerable to fluid contamination. In addition, a poppet valve with a high force/friction ratio (FFR) can increase a safety factor tenfold.
  2. Valves with a wet armature design can allow moisture and other impurities to enter the core tube area, causing the valves to stick.

Selecting valves with a dry armature and a diaphragm that isolates the media (air or gas) from the armature keeps moisture and contaminants out.

  1. Sometimes residual magnetic force will cause valves with wet armature to stick open when the coil is de-energized because there is insufficient internal power to move the coil.

Valves with robust spring force address this problem. A leading solenoid valve on the market has a 4.7kg spring, two to five times the next closest valve.

Selecting a valve with a more efficient magnetic path overcomes this problem as well. This includes both the design and materials. A smaller gap between the armature and core reduces the current needed to maintain the magnetic flux against the spring. And soft magnetic materials mean the drop out is very reliable. This combination makes the valve very snappy on changeover, both opening and closing.

  1. Pilot-operated valves often have a pilot mechanism with small vent ports that can allow internal moisture to infiltrate, causing contamination and internal corrosion. Again, when the valve is de-energized, there is not enough internal power to move the coil, leaving it stuck open.

This is another sticky situation where selecting direct-acting poppet valves with high FFR is the solution. These valves require no minimum supply pressure, so they will reliably close when de-energized.

Selecting a solenoid with the right design and construction allows operators to protect processes and systems from failure caused by sticky solenoids

 

What safety considerations should be taken into account when installing and operating solenoid valves?

It is recommended to install the valve in a dry and ventilated environment as during usage, the valve does get hot. Most solenoid valves can be used in one flow direction only. Be aware of the flow direction of the medium when installing the valve. An arrow on the valve body often indicates the correct flow direction.

 

Related Posts